Project objectives and scope
Plant capacity: Gross 50 MWe / Net 45–47 MWe
Design life: ≥ 25 years continuous operation
Site conditions: ambient temperature, humidity, rainfall, seismic zone, soil properties
Operating regime: Base load, >7,500 hours/year
International codes: ASME, ASTM, IEC, ISO, NFPA, EN
National standards: Thai ERC, PCD (Pollution Control Department), IEAT
Grid interconnection: PEA/EGAT Grid Code compliance
Occupational health & safety: OSHA/ILO guidelines
Engineering: basic & detailed design
Procurement: equipment, auxiliaries, spare parts, consumables
Construction & Erection: civil, mechanical, electrical, I&C
Commissioning & Performance Tests
Documentation & Training
Warranty and O&M support (minimum 2 years)
Fuel specification:
Rice Straw: 70–90% share, moisture ≤25%, LHV ~12–14 MJ/kg, high SiO₂ ash
Sugarcane Leaves: 10–30% share, moisture ≤30%, LHV ~10–12 MJ/kg
Fuel receiving, weighbridge, and quality control
Bale breaker, shredders, magnetic separators, stone traps
Covered fuel storage (≥ 7 days stock) + day bunker (≥ 12 hours stock)
Blending system with belt weigh feeders
Dust suppression, spark detection, fire protection, ATEX/NFPA compliance
Boiler type: Bubbling Fluidized Bed (BFB) or Circulating Fluidized Bed (CFB)
Fuel flexibility: designed for ≥ 90% rice straw firing capability
Steam parameters: 110–130 bar, 520–540 °C
Boiler efficiency: ≥ 88% HHV basis
Combustion air system: FD, ID, PA fans with VFDs
Bed material handling, ash coolers
Additive injection (Kaolin/Al-silicate, Ammonium Sulfate) for alkali & chloride control
Soot blowing (steam/air/sonic)
Start-up burners (diesel/gas)
Steam turbine type: Multistage condensing, single extraction
Net plant output: 45–47 MWe guaranteed
Heat rate: ≤ 11,500 kJ/kWh (net, LHV basis)
Generator: 11–15 kV, 50 Hz, air/hydrogen cooled
Lubrication and seal oil systems
Turbine hall with EOT crane
Surface condenser with titanium/stainless tubes
Cooling system: Mechanical draft cooling tower or Air-Cooled Condenser (ACC) depending on site water availability
Cooling water treatment (anti-scale, biocide)
CW pumps, make-up water system
Multicyclone dust separator
Main dust collection: Baghouse (preferred) or ESP
Dry/semi-dry scrubbing with hydrated lime for SO₂/HCl
Activated Carbon Injection for heavy metals & dioxins
NOx reduction: SNCR (urea/ammonia), provision for SCR optional
Continuous Emission Monitoring System (CEMS): NOx, SO₂, CO, O₂, PM, HCl, Hg
Bottom/bed ash handling system with cooling
Pneumatic conveying of fly ash to silos
Ash silos with truck loading spouts, dust suppression
Provision for ash utilization (cement, silica extraction) and disposal plan
Raw water treatment (MMF/UF)
Demineralization plant (RO + EDI or mixed bed)
Boiler feedwater: deaerator, dosing systems
Condensate polishing unit (optional)
Wastewater treatment plant (neutralization, settling, biological if required)
Zero Liquid Discharge (ZLD) concept preferred
Generator Step-Up Transformer (11/115 kV or 22/115 kV)
MV/HV switchgear, protection relays
Auxiliary transformers, LV MCCs, UPS, emergency diesel generator (EDG)
Earthing and lightning protection system
SCADA/EMS interface with utility
Compliance with PEA/EGAT grid code
Distributed Control System (DCS) with redundancy
Safety Instrumented System (SIS/ESD)
Field instruments (temperature, pressure, flow, level, vibration, gas analyzers)
Historian, data trending, cyber security protocols
Remote monitoring capability
Foundations and piling
Boiler house, turbine hall, control building, fuel storage sheds
Internal roads, stormwater drainage, firefighting water storage
Administrative building, workshop, warehouse
Compliance with OSHA, NFPA, Thai law
Fire detection and firefighting systems (hydrants, sprinklers, deluge, foam)
Explosion venting/dust explosion protection
Noise control (≤85 dBA at boundary)
Environmental monitoring plan (air, water, noise, waste)
Commissioning procedures and schedule
Performance tests:
Net Output Guarantee (≥45 MWe)
Net Heat Rate Guarantee (≤11,500 kJ/kWh)
Emission Guarantees (meet Thai PCD or stricter: PM ≤50 mg/Nm³, NOx ≤200 mg/Nm³, SO₂ ≤100 mg/Nm³)
Reliability run (≥72 hours continuous)
Availability guarantee (≥92% annual)
Liquidated damages (LDs) for shortfalls
O&M manuals, as-built drawings, spare parts list
Plant data books and certificates
Training programs for Owner’s staff (classroom + on-site)
Provision of simulator training (optional for >50 MWe plants)